High Pressure CO2 Automatic Fire Extinguishing System |
|
In the 1950s, the Soviet union began to help our country use the carbon
dioxide extinguishing system in the construction of the project. In
1977, the domestic carbon dioxide automatic fire extinguishing system
was approved by the state. Since then, the co2 automatic fire
extinguishing technology rapid development, now co2 automatic fire
extinguishing system in the domestic no matter in production or in
product applications belong to a fire extinguishing technology is very
mature.
Carbon dioxide is a non - conducting, inert, low-toxicity,
fire-extinguishing agent with good source, reputation and low price.
Carbon dioxide extinguishing is mainly the asphyxiation, and has a small
cooling effect. It is widely used in power plant, power station, mill,
printing plant, impregnated oil tank, paint, pharmaceutical and other
fire protection.
Co2 automatic fire extinguishing system is mainly composed of: gas fire
extinguishing alarm control system, fire detection systems, fire
extinguishing agent storage bottles, container valves, selector valve,
check valve, pneumatic control valve, pressure switch, nozzle, pipeline
and other major equipment. Can be a unit independent system or a
combination distribution system and other forms.
System technical parameters
The system model
QMW70 - SA
CO2Storage pressure of extinguishing agent bottle group
5.17MPa
Volume of extinguishing agent bottle
70L
CO2Filling quantity
42KG/bottle
CO2Monitoring of extinguishing agent bottle group
Automatic weighing
Storage device leakage boundary
10%
Extinguishing agent bottle group sealing form
Diaphragm seal
Storage pressure of N2 - driven gas cylinder group
6MPa
N2 drives gas cylinder volume
4L
N2 - drive gas cylinder group monitoring
Pressure gauge
Drive gas cylinder group seal form
Diaphragm seal
System startup mode
Automatic, electric manual emergency start, mechanical emergency manual three control modes
Rack form
Single arrangement, double arrangement
Fire extinguishing way
All submerged and partially submerged
Ambient temperature
0℃~+50℃
System delay start time
0~30s
Start voltage, current
DC24V,1.5A
Color of extinguishing agent bottle group
red
N2 drives gas cylinder group color
black
Bottle color
grey
Extinguishing agent storage bottle
High pressure seamless
Drive gas storage tanks
High pressure seamless
Single bottle load (containing agents)
About 140 kg
Arrange the size of the bottle
H=2163mm L=n*300+160mm W=760mm
Double row bottle size
H=2163mm L=n*300+160mm W=1350mm
Nozzles are nominal working pressure
1.4±0.1MPa
Pressure relief device of collector tube
15±0.75MPa
Collector's anticorrosion
Hot galvanizing
Storage container safety relief device action pressure
19±0.95MPa
The main physical and chemical parameters of carbon dioxide
Chinese name
Carbon dioxide
Melting point
-56.55℃(216.6K)
English name
carbon dioxide
The boiling point
-78.45℃(194.7K)
Chemical formula
CO2
Water soluble
1.45 g/L(25℃,100kPa)
The molecular weight
44.0095
The density of
gas1.977g/L,liquid1.816kg/L
CAS Log in
124 - 38 - 9
appearance
Colorless and odorless gas
EINECS Log in
204 - 696 - 9
Flash point
n.
The main physical and chemical parameters of carbon dioxide
High pressure carbon dioxide composite distribution of gas fire pipe network axis