HFC-227ea The Reservoir Pressure Automatic Fire Extinguishing System |
|
HFC-227ea Is a predominantly chemical fire extinguishing, both physical and fire
extinguishing effect of the clean gas fire extinguishing agent,
(chemical fire extinguishing: halogen atoms in the active group in which
the minimum radius of fluorine free radicals, can be a very good
capture active group H + and OH - in combustion; Physical extinguishing:
mainly cooling effect; It is beneficial to protect the delicate
electronic equipment and valuables from the gaseous, colorless,
odorless, low-toxic, non-conductive, non-polluting and protected objects
in the gas phase of normal temperature. The storage space is small, the
critical temperature is high, the critical pressure is low, and it can
be liquefied under normal temperature. No particle or oil residue after
casting, no damage to the ozone layer (ODP value is zero), and the
duration of stay in the atmosphere is 31 ~ 42 years, which meets
environmental requirements. The concentration of non-toxic reaction
(NOAEL) of sevoflurane was 9%, and the concentration of toxic reaction
(LOAEL) was 10.5%, while the concentration of sevoflurane was generally
less than 10%, which was safe for human body. |
|
System technical parameters
Product model |
QMQ4.2/90N-SA |
QMQ4.2/120N-SA |
QMQ4.2/150N-SA |
Storage pressure of the flurane extinguishing agent bottle group |
4.2MPa |
||
Volume of extinguishing agent bottle |
90L |
120L |
150L |
Monitoring of extinguishing agent bottle group |
Pressure gauge |
||
Extinguishing agent bottle group sealing form |
Diaphragm seal |
||
N2 drives gas cylinder volume |
4L |
||
N2 - drive gas cylinder group monitoring |
Pressure gauge |
||
Drive gas cylinder group seal form |
Diaphragm seal |
||
System startup mode |
Automatic, electric manual emergency start, mechanical emergency manual and emergency stop four control modes |
||
Rack form |
Single arrangement, double arrangement |
||
Fire extinguishing way |
Total flooding |
||
Ambient temperature |
0℃~+50℃ |
||
System delay start time |
0~30s |
||
Start voltage, current |
DC24V,1.5A |
||
Color of extinguishing agent bottle group |
red |
||
N2 drives gas cylinder group color |
black |
||
Bottle color |
grey |
||
Extinguishing agent storage bottle |
welding |
||
Drive gas storage tanks |
High pressure seamless |
||
The weight of the |
|
|
|
Arrange the size of the bottle |
H=1750mmL=n*400+320mmW=850mm |
H=2050mmL=n*400+320mmW=850mm |
H=2000mmL=n*440+340mmW=880mm |
Double row bottle size |
H=1750mmL=n*400+320mmW=1140mm |
H=2050mmL=n*400+320mmW=1140mm |
H=2000mmL=n*440+340mmW=1200mm |
Nozzles are nominal working pressure(MPa) |
1.4±0.1MPa |
||
The pressure of the safety discharge device of the collector tube(MPa) |
7.2±0.36MPa |
||
Collector's anticorrosion |
Hot and cold galvanized inside and outside |
||
Storage container safety relief device action pressure(MPa) |
7.2±0.36MPa |
The axial profile of the gas fire-extinguishing pipe network was distributed by the internal storage pressure
Schematic diagram of the gas fire extinguishing system of the internal storage pressure type seflurane