Marine CO2 fire extinguishing system |
|
|
Marine CO2 fire extinguishing system Using high pressure storage, cast hand control and remote control way,
when the environment temperature - 10 ~ 50 ℃, system maximum working
pressure is 14.7 Mpa. System performance to meet the international
convention on the safety of life at sea, and the request of
"international safety rules of fire control system, and satisfy our
country ships and inland steel ship classification society and ship
inspection bureau construction rules (CCS and ZC) requirement, ship
carbon dioxide extinguishing equipment my company has obtained the
recognition of CCS in China. |
Manufacturing Standards
Marine standards《Marine carbon dioxide extinguishing equipment》CB/T 3294 - 1988
Maritime bureau of the People's Republic of China《Technical rules for the statutory inspection of inland waterways》(2011)
China classification society(CCS)《Specifications for the classification of steel sea-ships》(2012)
|
|
|
System technical parameters |
Model |
ZE70/C-SA ZE70/C-N-SA |
Model |
ZE70/C-SA ZE70/C-N-SA |
||
Type |
Fix type |
In the form of |
stationary |
||
Nominated pressure |
14.7Mpa |
Nominal pressure |
14.7Mpa |
||
Volume of gas cylinder Filling ratio |
CO2 1 cylinder |
68L |
The cylinder volume |
Carbon dioxide cylinders |
68L |
N2 cylinder |
4L |
Nitrogen cylinders |
4L |
||
≤0.67Kg/L |
Filling rate |
≤0.67Kg/L |
|||
Ambient conditions |
Ambient temperature |
-10℃+50℃ |
Environmental conditions |
environment temperature |
-10℃+50℃ |
Relative humidity |
93±3% |
Relative humidity |
93±3% |
||
Usage power |
Main power |
AC220V 50HZ |
Use the power supply |
The main power supply |
AC220V 50HZ |
Standby power |
DC24V 3A |
For the power supply |
DC24V 3A |
||
Consumption power |
During alert |
≤30W |
Consumed power |
When the alert |
≤30W |
During work |
200W |
working |
200W |
||
Operation mode |
Pneumatic |
Remote |
Mode of operation |
pneumatic |
Remote control |
Manual |
Onsite operation |
manual |
On-site operation |
||
Emergency operation |
Onsite operation |
Emergency operation |
On-site operation |
||
Release delay |
Mechanical delay |
20~40S |
Cast time delay |
Mechanical delay |
20~40S |
Start gas source |
Usage gas |
N2 |
Start the power supply |
The use of gas |
N2 |
|
Filled gas |
5.9MPa |
|
Filling pressure |
5.9MPa |
Overall dimension
Type
|
Qty
|
L
|
W
|
H
|
Type
|
Qty
|
L
|
W
|
H
|
Type
|
Qty
|
L
|
W
|
H
|
Singlerow Singlerelease |
2 |
685 |
350 |
2000 |
Doublerow
Singlerelease
|
4 |
685 |
660 |
2000 |
Doublerow Doublerelease |
4 |
685 |
680 |
2000 |
3 |
975 |
6 |
975 |
6 |
975 |
|||||||||
4 |
1265 |
8 |
1265 |
8 |
1265 |
|||||||||
5 |
1555 |
10 |
1555 |
10 |
1555 |
|||||||||
6 |
1845 |
12 |
1845 |
12 |
1845 |
|||||||||
7 |
2135 |
14 |
2135 |
14 |
2135 |
|||||||||
8 |
2425 |
16 |
2425 |
16 |
2425 |
|||||||||
9 |
2715 |
18 |
2715 |
18 |
2715 |
|||||||||
10 |
3005 |
20 |
3005 |
20 |
3005 |
|
Principle diagram of ZE70 / c-n-sa Marine carbon dioxide of marine carbon dioxide fire extinguishing system |
1、Fire alarm box | 2、The nozzle | 3、Pressure signal transmitter | 4、Valve casting | 5、Back pressure valve | 6、Signal called flute | 7、Cylinder assembly | 8、Remote control casting station | 9、Travel switch | 10、Purge valve
|
Principle diagram of ZE70 / c-sa Marine carbon dioxide extinguishing marine carbon dioxide fire extinguishing system |
1、Fire alarm box | 2、The nozzle | 3、Pressure signal transmitter | 4、Valve casting | 5、Back pressure valve | 6、Signal called flute | 7、Cylinder assembly | 8、Remote control casting station | 9、Travel switch | 10、Purge valve