| High Pressure CO2 Automatic Fire Extinguishing System |  | 
	 
 
	
	 
	 
						In the 1950s, the Soviet union began to help our country use the carbon 
dioxide extinguishing system in the construction of the project. In 
1977, the domestic carbon dioxide automatic fire extinguishing system 
was approved by the state. Since then, the co2 automatic fire 
extinguishing technology rapid development, now co2 automatic fire 
extinguishing system in the domestic no matter in production or in 
product applications belong to a fire extinguishing technology is very 
mature. 
					 
						 
						Carbon dioxide is a non - conducting, inert, low-toxicity, 
fire-extinguishing agent with good source, reputation and low price. 
Carbon dioxide extinguishing is mainly the asphyxiation, and has a small
 cooling effect. It is widely used in power plant, power station, mill, 
printing plant, impregnated oil tank, paint, pharmaceutical and other 
fire protection. 
					 
						 
						Co2 automatic fire extinguishing system is mainly composed of: gas fire 
extinguishing alarm control system, fire detection systems, fire 
extinguishing agent storage bottles, container valves, selector valve, 
check valve, pneumatic control valve, pressure switch, nozzle, pipeline 
and other major equipment. Can be a unit independent system or a 
combination distribution system and other forms. 
					
		
			
 
				 
		
	
					 
				
					
					
					 
			
				
	
	 
	
		
			
				 
		
	
					 
				
				
					    System technical parameters 
				 
			
 
	 
	
		
			
				 
			
					    The system model 
				
				
					    QMW70 - SA 
			
				
				 
			
					    CO2Storage pressure of extinguishing agent bottle group       
				
				
					    5.17MPa 
			
				
				 
			
					    Volume of extinguishing agent bottle 
				
				
					    70L 
			
				
				 
			
					    CO2Filling quantity 
				
				
					    42KG/bottle 
			
				
				 
			
					    CO2Monitoring of extinguishing agent bottle group 
				
				
					    Automatic weighing 
			
				
				 
			
					    Storage device leakage boundary 
				
				
					    10% 
			
				
				 
			
					    Extinguishing agent bottle group sealing form 
				
				
					    Diaphragm seal 
			
				
				 
			
					    Storage pressure of N2 - driven gas cylinder group 
				
				
					    6MPa 
			
				
				 
			
					    N2 drives gas cylinder volume 
				
				
					    4L 
			
				
				 
			
					    N2 - drive gas cylinder group monitoring 
				
				
					    Pressure gauge 
			
				
				 
			
					    Drive gas cylinder group seal form 
				
				
					    Diaphragm seal 
			
				
				 
			
					    System startup mode 
				
				
					    Automatic, electric manual emergency start, mechanical emergency manual three control modes 
			
				
				 
			
					    Rack form 
				
				
					    Single arrangement, double arrangement 
			
				
				 
			
					    Fire extinguishing way 
				
				
					    All submerged and partially submerged 
			
				
				 
			
					    Ambient temperature 
				
				
					    0℃~+50℃ 
			
				
				 
			
					    System delay start time 
				
				
					    0~30s 
			
				
				 
			
					    Start voltage, current 
				
				
					    DC24V,1.5A 
			
				
				 
			
					    Color of extinguishing agent bottle group 
				
				
					    red 
			
				
				 
			
					    N2 drives gas cylinder group color 
				
				
					    black 
			
				
				 
			
					    Bottle color 
				
				
					    grey 
			
				
				 
			
					    Extinguishing agent storage bottle 
				
				
					    High pressure seamless 
			
				
				 
			
					    Drive gas storage tanks 
				
				
					    High pressure seamless 
			
				
				 
			
					    Single bottle load (containing agents) 
				
				
					    About 140 kg 
			
				
				 
			
					    Arrange the size of the bottle 
				
				
					    H=2163mm L=n*300+160mm W=760mm 
			
				
				 
			
					    Double row bottle size 
				
				
					    H=2163mm L=n*300+160mm W=1350mm 
			
				
				 
			
					    Nozzles are nominal working pressure 
				
				
					    1.4±0.1MPa 
			
				
				 
			
					    Pressure relief device of collector tube 
				
				
					    15±0.75MPa 
			
				
				 
			
					    Collector's anticorrosion 
				
				
					    Hot galvanizing 
			
				
				 
		
	
					    Storage container safety relief device action pressure 
				
				
					    19±0.95MPa 
			
				
 
	 
	
		
			
				 
		
	
					 
				
				
					    The main physical and chemical parameters of carbon dioxide 
				 
			
 
	 
	
		
			
				 
			
					    Chinese name 
				
				
					    Carbon dioxide 
				
				
					    Melting point 
				
				
					    -56.55℃(216.6K) 
			
				
				 
			
					    English name 
				
				
					    carbon dioxide 
				
				
					    The boiling point 
				
				
					    -78.45℃(194.7K) 
			
				
				 
			
					    Chemical formula 
				
				
					    CO2 
				
				
					    Water soluble 
				
				
					    1.45 g/L(25℃,100kPa) 
			
				
				 
			
					    The molecular weight 
				
				
					    44.0095 
				
				
					    The density of 
				
				
					    gas1.977g/L,liquid1.816kg/L 
			
				
				 
			
					    CAS Log in 
				
				
					    124 - 38 - 9 
				
				
					    appearance 
				
				
					    Colorless and odorless gas 
			
				
				 
		
	
					    EINECS Log in 
				
				
					    204 - 696 - 9 
				
				
					    Flash point 
				
				
					    n. 
			
				
 
	 
	
		
			
				 
		
	
					 
				
				
					    The main physical and chemical parameters of carbon dioxide 
				 
			
 
	
 
	 
	
		
			
				 
		
	
					 
				
				
					    High pressure carbon dioxide composite distribution of gas fire pipe network axis 
				 
			
 
	
 










 
                